Air-liquid CDU, a rapidly deployable liquid-cooled server, dissipates heat to the computer room through air-liquid heat exchange without the need to retrofit the existing air-cooled computer room. The 6U chassis can support a liquid-cooled server load of up to 13kW.
Wind-liquid CDU solution, quickly deploy liquid-cooled servers in existing air-cooled computer rooms.
Installed in a 19-inch standard rack with a 6U height, suitable for most computer room racks.
In a computer room with an ambient temperature of 25°C, it can provide a liquid-cooling load of 13kW.
The optimized heat exchanger design requires a smaller temperature difference. When the ambient temperature is 25°C, the supply liquid temperature is not higher than 40°C.
Stainless steel pipes and all-copper heat exchangers offer better wetted material compatibility and are compatible with commonly used coolants.
Dual-pump design provides 1+1 redundancy, with automatic speed adjustment to supply the required coolant flow.
Dual-fan design automatically adjusts the air volume to minimize operating noise as much as possible.
Dual-power supply design provides 1+1 redundancy to ensure the safe and stable operation of the equipment.
High-density coolant filter provides precise protection for server cold plates and quick connectors.
Real-time monitoring of computer room temperature, equipment outlet air temperature, coolant supply liquid temperature, coolant supply and return water pressure, and real-time control of coolant flow and temperature.
The real-time display of the system operating status, system alarms, status, self-check and other information can be read and operated through a 7-inch touch screen.
Remote monitoring is achieved through TCP/ModBUS.
Automatic/manual water replenishment system, easy for delivery, commissioning, operation and maintenance.